NOTICE TO INSTALLER: Instructions must remain with installation.
Product information presented
here re fl ects con di tions at time
of publication. Consult factory
re gard ing dis crep an cies or
in con sis ten cies.
BATTERY BACKUP PEDESTAL SUMP PUMP
1. Inspect your pump. Occasionally, products are dam aged during shipment. If the unit or any of the parts are dam aged, contact your dealer
before us ing.
2. Read all the installation instructions regarding in stall ing and start up. Retain for future ref er ence.
1. Testing for Ground. As a safe ty mea sure each elec tri cal outlet
should be checked for ground using an Underwriters Laboratory
list ed cir cuit ana lyzer, which will indicate if the power, neu tral and
ground wires are correctly con nected to your out let. If they are
not, call a qualifi ed licensed electrician.
2. For your pro tec tion always dis con nect the pow er supply from
its power source before handling the com po nents of your DC
back up pump or the pri ma ry pump.
3. Installation and checking of elec tri cal cir cuits and hard ware should
be per formed by a qualifi ed, li censed electrician.
1. Make sure there is a properly ground ed 115V re cep tacle avail-
able. Do not use primary pump cir cuit. The location must be within
6' of the control box and battery. The power supply for your DC
control system plugs directly into the 115V outlet. DO NOT USE
AN EX TEN SION CORD.
2. Make sure the 115V electrical supply circuit is equipped
with fuses or circuit breakers of prop er capacity.
3. DC emergency pumps are de signed for han dling clear water. Do
not use in septic tanks to pump ef fl u ent or sew age pits to pump
sewage.
4. Repair and service of your DC backup sys tem should be per formed
by an authorized service station.
P.O. BOX 16347 • Louisville, KY 40256-0347
3649 Cane Run Road • Louisville, KY 40211-1961
(502) 778-2731 • 1 (800) 928-PUMP • FAX (502) 774-3624
MODELS 580 & 585
PREINSTALLATION CHECKLIST
SEE BELOW FOR LIST OF WARNINGS
SEE BELOW FOR LIST OF CAUTIONS
© Copyright 2009 Zoeller Co. All rights reserved.
4. All elec tri cal and safety codes must be fol lowed in ad di tion to the
National Electrical Code and all applicable local codes.
5.
It is the owner's responsibility to check the bat tery
and bat tery connection at least once a month. Bat-
ter ies con tain acid and cau tion must be taken when
han dling.
6. Risk of electric shock - These pumps have not been investigated
for use in swimming pool areas.
7. According to the state of California (Prop 65), this product contains
chemicals known to the state of California to cause cancer and
birth defects or other reproductive harm.
5. The installation of DC automatic back up pumps re quires the use
of a variable level fl oat switch for operation. It is the responsibility
of the installing party, to ensure that the teth ered fl oat switch will
not hang up on the pump ap pa ra tus or pit pe cu li ari ties and is
secured so the pump will turn "on" and "off". It is recommended
that the pit be 18" in diameter or larger to ac com mo date both a
pri ma ry and a DC backup pump.
REFER TO WARRANTY ON PAGE 2.
SECTION: 6.10.079
FM1613
Supersedes
visit our web site:
www.zoeller.com
0609
0409

Advertisement

Table of Contents
loading

Summary of Contents for Zoeller AQUANOT 585

  • Page 1 fl u ent or sew age pits to pump sewage. REFER TO WARRANTY ON PAGE 2. 4. Repair and service of your DC backup sys tem should be per formed by an authorized service station. © Copyright 2009 Zoeller Co. All rights reserved.
  • Page 2: Limited Warranty

    Some of these by-products can produce a rotten egg odor. Also, some of these by-products can cause a CO detector to falsely activate. In order to help prevent false activation, Zoeller recommends moving the battery as far apart from the CO detector as possible or, if necessary, vent the battery to the exterior.
  • Page 3: Performance Characteristics

    Gal. Liters GALLONS LITERS FLOW PER MINUTE Shut-off Head: 17 ft.(5.2m) 011922 Note: Aquanot ® II (Model 585) data was de vel oped with the charger supplying DC power to the pump. © Copyright 2009 Zoeller Co. All rights reserved.
  • Page 4 STOP "ADJUST" ON/OFF POSITIONS UPPER "ON" STOP HEIGHT "OFF" MAIN DISCHARGE FLOAT ROD HEIGHT LOWER LINE STOP GUIDE PRIMARY PUMP LOWER STOP "ON" HEIGHT "OFF" HEIGHT Figure 2.1 Figure 2.2 SK1776 SK1777 © Copyright 2009 Zoeller Co. All rights reserved.
  • Page 5 6.6) If the pump is not operating properly after following the above steps, refer to the Troubleshooting guide on page 8. 6.7) When fi nished testing plug primary pump back into AC receptacle. © Copyright 2009 Zoeller Co. All rights reserved.
  • Page 6 There are millions of batteries manufactured each year, so it is impossible to guarantee consistent quality. A defective battery will never become fully charged and may damage the circuits of the charger. It is for this reason that Zoeller offers its own line of batteries.
  • Page 7: Illustrated Parts Breakdown

    Factory *Advise motor Leeson or CIM. If the following checklist does not solve the prob lem, con sult Zoeller’s Before servicing a pump, always shut off the main Technical Service De part ment 1-(800) 928-7867 - Do not at tempt to pow er breaker and then unplug the pump - making sure you service or oth er wise dis as sem ble pump.
  • Page 8: Troubleshooting Guide

    TO BATTERY. Defective controller. Contact factory. Have battery inspected. The charger will over charge a ROTTEN EGG SMELL IN BASEMENT. Charger is overcharging battery. battery with a defective cell. © Copyright 2009 Zoeller Co. All rights reserved.

This manual is also suitable for: